概要

開発元はこのテキストをお使いの言語で提供していません。

PID Tuner uses the IMC (Internal Model Control) method to calculate PID tuning parameters. I’ve tried a lot of tuning methods over the years and have found this one to be the best. The app is written for the iPad to show all the information on one page.

The program calculates:

PID Parameters:
Controller Gain (Kc)
Integral Time (Ti)
Derivative Time (Td)

For process types
First Order with Dead Time (FO)
Second Order with Dead Time (SO)
Integrating or Long Time Constant with Dead Time (I)

For controller types
Parallel (non-interacting)
c(s) = Kc (1 + 1/(Ti s) + Td s)
Series (interacting)
c(s) = Kc (Ti s + 1)/(Ti s)(Td s + 1)

For controller modes
PID
PI

You can either enter the process gain (Kp) directly or enter the changes in the controlled virable (CV) and manipulated variable (MV).

Tuning aggression is adjusted using the slider to set the closed loop time constant to the process time constant ratio (λ/Ƭ).

The closed loop time constant (λ) is the time the controller is expected to reach set point (plus the dead time (ϴ)). Setting the closed loop time constant to process time constant ratio (λ/Ƭ) to 1.0 will make the MV change to its final value and allow the process to settle out to the setpoint. Setting (λ/Ƭ) greater than 1.0 will give a slower responce. Setting (λ/Ƭ) less than 1.0 will cause the MV to make a larger change and then reduce to its final value. Tight tuning would be to set the close loop time constant to the dead time.

Use the Integrating Process type (Ƭ = ∞) for both integrating processes or processes with long time constants. These processes use the maximum slope as the process gain. Tuning aggression for these processes is determined by setting the closed loop time constant to the dead time ratio (λ/ϴ). Once again, setting the closed loop time constat to the dead time gives tight control.

References:

“Probably the test simple PID tuning rules in the World,” Sigurd Skogestad, Jounal of Process Control, July 3, 2001

“Consider the generalized IMC-PID method for PID controller tuning of time-delay processes,” Y. Lee, S. Park, M. Lee, Hydrocarbon Processing, January 2006

新機能

バージョン 3.6 · 2024/9/25

Fixed a plot scaling problem in the iPad simulator

アプリのプライバシー

このアプリのデータの取り扱いについて、Richard H StreetがApp Storeで申告している内容です。

  • データの収集なし

    開発元はこのアプリからデータを収集しません。

プライバシーの取り扱いは、ご利用の機能やお客様の年齢などに応じて異なる場合があります。

情報

販売元
Richard H Street
カテゴリ
ユーティリティ
バージョン
3.6
更新日
2024/9/25
リリース
2015/10/13
サイズ
1.1 MB
必要条件
iOS 15.0以降
対象年齢
4+
価格
¥800
言語
英語
著作権
© 2015 Rick Street